Section 14-00: Battery and Charging System—Service
1994 Mustang Workshop Manual
DIAGNOSIS AND TESTING

Component Tests

 
 

Battery

Maintenance-Free Batteries

Read the battery open circuit terminal voltage with a digital voltmeter such as Rotunda Digital Volt-Ohmmeter 007-00001 or equivalent, capable of reading 1/100 volt. If open circuit voltage of battery (10653) is below 12.4 volts and the battery has passed the capacity test, charge the battery .

NOTE: Whenever possible, test and charge battery at or near room temperature.

  1. Use a high rate discharge tester with a variable rate control or a fused rate tester with meter compensation for different battery electrical sizes. Follow instructions supplied with tester for the battery capacity test.
  1. Recommended discharge rate at 27°C (80° F): one-half of the cold cranking amps.

    Cold Cranking Amps Discharge Rate Amps
    650 325
    540 270

  1. Voltage readings at 15 seconds for good battery (Battery Capacity Test).

    Approximate Battery Temperature Minimum Load Voltage
    27°C(80°F) and above 9.6
    21°C(70°F) 9.6
    16°C(60°F) 9.5
    10°C(50°F) 9.4
    4°C(40°F) 9.3
    -1°C(30°F) 9.1
    -7°C(20°F) 8.9
    -12°C(10°F) 8.7
    -18°C(0°F) 8.5

  1. Wait two minutes and check the Open Circuit Voltage (OCV).
  1. Measure OCV with a digital voltmeter capable of reading 1/100 volt.
 

Drain Test

Check for current drains on the battery in excess of 100 milliamps with all the electrical accessories off and the vehicle at rest. Current drains can be tested one of three ways:

  1. Connect a 12-volt test lamp in series with battery positive terminal. If lamp glows, then a drain exists.
  1. Use an in-line ammeter between the battery positive or negative post and its respective cable.
  1. Use a clamp-on current probe to the battery positive or negative cable. Make sure that the probe is properly calibrated to prevent false readings.



    Typically, a drain of approximately one amp can be attributed to an engine compartment lamp, glove compartment lamp, or luggage compartment lamp staying on continually. Other component failures or wiring shorts may be located by selectively pulling fuses or disconnecting fuse links to pinpoint the location of the current drain. When the current drain is found, the test lamp will go out or the meter reading will fall to an acceptable level. If the short is still not located, after checking all the fuses and fuse links, the drain may be due to the generator (GEN) (10346) /generator regulator (10316). Disconnect the generator output wire from the output stud and the generator regulator connector. If this eliminates the drain, check the charging system to locate the concern.

    NOTE: A voltmeter is sometimes used for this test but it will react to a very small normal drain caused by "always-on" electronic systems such as starter interlock, anti-theft alarm, illuminated entry, etc, which cause no concern. The test lamp shows only drains which are large enough to cause a concern.

 

Battery Capacity Testing

With Clamp On DC Ammeter

Test Procedure

  1. Turn the ignition switch (11572) to the OFF position and make sure there are no electrical loads. After determining that the engine compartment lamp is turning off properly, disconnect the lamp.
  1. Clamp the meter clip securely around positive or negative battery cable (all cables if two or more lead to post).

    NOTE: Do not start vehicle with clip on cable.

 

Test Conclusion

The current reading (current drain) should be less than 0.05 amp. If it exceeds 0.05 it indicates a constant current drain which could cause a discharged battery . Possible sources of current drain are vehicle lamps (engine compartment, glove compartment, luggage compartment, etc.) that do not shut off properly.

If the drain is not caused by a vehicle lamp, remove fuses from the fuse panel, one at a time, until the cause of the drain is located. If drain is still undetermined, remove fusible links one at a time at the power distribution box contained within the headlamp dash panel junction wire (14290) to find the problem circuit.

 

With Voltmeter

This test requires a digital volt-ohmmeter with an appropriate low voltage scale such as Rotunda Digital Volt-Ohmmeter 007-00001 or equivalent. The meter must read within 0.01 millivolt. Also required is a shunt assembly similar to that shown in the illustration.

 

Test Procedure

  1. Turn ignition switch to the OFF position and make sure there are no electrical loads. After determining the engine compartment lamp is turning off properly, disconnect the lamp.
  1. Check battery voltage. If voltage is under 11.5 volts, charge the battery to above 11.5 volts.
  1. Disconnect battery ground cable (14301) .

    NOTE: When the battery is disconnected and reconnected, some abnormal drive symptoms may occur while the powertrain control module (PCM) (12A650) relearns its adaptive strategy. The vehicle may need to be driven 10 miles or more to relearn the strategy.

  1. Connect shunt assembly as shown.

     CAUTION: Do not crank the engine, it could destroy the shunt. Also do not use the shunt to measure starting currents.

  1. Set volt-ohmmeter to 200 or 300 mv scale for an accurate reading (must be within 0.01 millivolt).
  1. Connect meter leads to shunt as shown. With this size shunt (50 mv = 50 amps) and meter, a direct current drain measurement can be made.



 

Test Conclusion

The current reading (current drain) should be less than 0.05 amp. If the reading is between 0.2 and 0.9 amp, a possible drain may be a vehicle lamp (glove compartment, engine compartment, luggage compartment, etc.) that does not turn off. If the cause of the drain is not a lamp, remove the fuses from the fuse panel one at a time until the cause of the drain is located. If drain is still undetermined, remove fuses one at a time at the power distribution box to find the problem circuit.

 

Electronic Drains Which Shut Off When the Battery Cable is Disconnected

  1. Repeat Steps 1 through 5 of the Battery Capacity Test with Voltmeter.
  1. Without starting engine, turn ignition switch to the RUN position for a moment and then OFF. If applicable, wait one minute for the illuminated entry lamps to turn off.
  1. Connect voltmeter and read voltage.
 

Test Conclusion

The current reading (current drain) should be less than 0.05 amp. If it exceeds 0.05 after a few minutes, and if this drain did not show in previous tests, the drain is most likely caused by a malfunctioning electronic component. As in previous tests, remove fuses in power distribution box one at a time to locate the problem circuit.

 

Generator On-Vehicle Tests

 

Troubleshooting or diagnosis is required before actual service can be made in the electrical system. Even where an obvious condition makes replacement of a component necessary, find out why the component failed. When a condition is diagnosed correctly, unnecessary service is prevented, the time the vehicle is out of service will be decreased, and the condition will be properly corrected the first time.

NOTE: Refer to the Rotunda VAT-40 test procedure manual for complete directions on checking out the charging system.

In order to check the charging system, the use of Rotunda Starting and Charging Tester (VAT-40) 078-00005 or equivalent tester is suggested.

When performing charging system tests, turn OFF all lamps and electrical components. Place transmission in NEUTRAL and apply parking brake.

 CAUTION: Do not make jumper wire connections except as directed. To do so may damage generator regulator .

NOTE: Battery posts and cable clamps must be clean and tight to ensure accurate meter indications.

 

Load Test

  1. Switch the Rotunda Starting and Charging Tester (VAT-40) 078-00005 or equivalent to the ammeter function.
  1. Connect the positive and negative leads of the Rotunda Starting and Charging Tester (VAT-40) 078-00005 or equivalent to the battery .
  1. Connect the current probe to the generator B+ output lead, Circuit 38 (BK/O).
  1. With the engine running at 2000 rpm, adjust the Rotunda Starting and Charging Tester (VAT-40) 078-00005 or equivalent load bank to determine the output of the generator . Generator output should be greater than the graph shown below. If not, refer to the Symptom Chart in this Section for diagnostic procedures.



 

No-Load Test

  1. Switch the Rotunda Starting and Charging Tester (VAT-40) 078-00005 or equivalent to the voltmeter function.
  1. Connect the voltmeter positive lead to the generator B+ terminal and the negative lead to ground.
  1. Turn all electrical accessories OFF.
  1. With the engine running at 2000 rpm, check the generator output voltage. The voltage should be between 13.0 and 15.0 volts. If not, refer to the Symptom Chart in this Section for diagnostic procedures.
 

Generator Bench Tests

NOTE: The integral rear mount regulator—internal fan type generator is serviced as an assembly only.

Replace generator as required after performing Generator On-Vehicle Tests. Refer to Section 14-02 for Removal and Installation procedures.