Section 12-00: Climate Control System—Service | 1993 Mustang Workshop Manual |
REFRIGERANT SYSTEM SERVICE
Refrigerant Recovery
Refrigerant recovery systems and recycling stations are in use in most
automotive A/C service facilities. The use of such equipment makes possible the
recovery and reuse of R-12 system refrigerant after contaminants and moisture
have been removed.
If a refrigerant recovery or recycling station is used, the following
general procedures should be observed, in addition to the operating
instructions provided by the equipment manufacturer.
CAUTION: Use extreme care and observe all safety and service precautions
related to the use of refrigerants.
- Connect refrigerant recycling station hose(s) to vehicle A/C service ports
and recovery station inlet fitting.
NOTE: Hoses should have shut off devices or check valves within 25.4cm (12
inch) of the hose end to minimize the introduction of non-condensable gases
(air) into the recycling station and to minimize the amount of refrigerant
released when the hose(s) is disconnected.
- Turn power to the recycling station on to start recovery process. Allow
recycling station to pump refrigerant from the system until the vehicle system
pressure goes into a vacuum. On some stations, the pump will be shut off
automatically by a low pressure switch in the electrical system. On other units
it may be necessary to manually turn off the pump.
- Once recycling station has evacuated vehicle A/C system, close the station
inlet valve (if so equipped). Then, switch off electrical power.
- Allow vehicle refrigerant system to remain closed for about two minutes.
Observe system pressure/vacuum level as shown on the gauge. If pressure does
not rise, disconnect recycling station hose(s).
- If system pressure rises, repeat Steps 2, 3 and 4 until the vacuum level
remains stable for two minutes.
- Perform required service operations, evacuate and recharge the A/C system.
Connecting the Manifold Gauge Set
Tools Required:
- Rotunda Adapter D81L-19703-A
- Turn both manifold gauge set valves all the way to the right to close the
high and low-pressure hoses to the manifold center hose. A Rotunda Adapter
D81L-19703-A, Motorcraft Tool YT-354 or 355 or equivalent must be used to
connect the manifold gauge set or charging station to the high-pressure service
gauge port valve.
- Remove the caps from the high and low-pressure service gauge port valves.
- If the manifold gauge set or charging station hoses do not have valve
depressing pins in them, install Fitting Adapters T71P-19703-S and R (which
have pins) on the low and high-pressure hoses.
- Connect the high and low-pressure hose adapters to the respective high and
low-pressure service gauge port valves. The adapter shown must be used on the
high-pressure gauge port valve.
System Discharging
Tools Required:
- Rotunda A/C Refrigerant Reclaim System 078-00800
In order to minimize the discharge of ozone depleting chlorofluorocarbons
into the atmosphere, the Ford Motor Company supports the efficient usage,
recovery and recycling of the R-12 used in passenger car, compact truck, and
light truck air conditioners. Ford Motor Company recommends the use of a
U.L.-approved recovery/recycling device such as Rotunda Model 078-00800 or
equivalent (which meets SAE Standard J 1991), during any A/C system repair and
recharge procedure which requires that the system be discharged.
System Evacuating
- Connect manifold gauge set as outlined, if not yet connected.
- Leak test the system as outlined.
- Remove the refrigerant from the system as outlined.
- Ensure both manifold gauge valves are turned all the way to the right.
- Ensure the center hose connection at the manifold gauge is tight (closed).
- Connect manifold gauge set center hose to a vacuum pump.
- Open manifold gauge set valves and start the vacuum pump.
- Evacuate the system with the vacuum pump until low-pressure gauge reads at
least 84.2 kPa (25 in.-Hg) (vacuum) and as close to 101.04 kPa (30 in.-Hg) as
possible. Continue to operate the vacuum pump for 30 minutes.
- When evacuation of system is complete, close manifold gauge set valves and
turn the vacuum pump off.
- Observe low-pressure gauge for a minimum of five minutes to ensure system
vacuum is held. If vacuum is held, charge the system. If vacuum is not held for
five minutes, leak test the system, service the leaks, and evacuate the system
again.
System Charging Set-Up
Ford Motor Company recommends using a charging station to perform
evacuation and charging of the refrigerant system. Follow the instructions
provided with the charging station.
If a charging station is not available, system charging may be
accomplished using a separate vacuum pump, charging cylinder and manifold gauge
set. The use of small cans of R-12 is NOT recommended.
If the charging cylinder method is used, the center port of the manifold
gauge set should have two refrigerant hoses with integral shut-off valves built
into the manifold gauge set. If the gauge set is the type that does not have
shut-off valves and two hoses at the center port, a tee fitting and two hoses
should be installed at the center port. In addition, the hoses attached to the
center port should have shut-off valves at the other ends of the two center
hoses to prevent air from entering the hoses when not connected to the vacuum
pump and charging cylinder.
Charging with a Charging Cylinder:
- If the vehicle suction (low) side service port is located on the
accumulator, connect the gauge set center hose to the liquid port of the
charging cylinder. If the suction (low) side service port is NOT on the
accumulator (located on the suction hose), connect the center hose to the GAS
port of the charging cylinder.
WARNING: LIQUID CHARGE INTO THE VEHICLE SUCTION ACCUMULATOR ONLY. TO PREVENT
COMPRESSOR SLUGGING, DO NOT LIQUID CHARGE INTO A REFRIGERANT HOSE WHILE THE
ENGINE IS OPERATING.
- When evacuating the system with the vacuum pump, the gauge set second
center hose should be connected to the charging cylinder and opened to the
gauge set so that the hose will evacuated with the system.
- When evacuation of the system is completed, close the center hose valve to
the vacuum pump and turn the pump off.
- Open the charging cylinder valve and the gauge set low side valve to allow
refrigerant to enter the system.
- When no more refrigerant is being drawn into the system, start the engine
and select an A/C function on the control assembly. Then, move the blower
function setting to high to allow the remaining refrigerant to be drawn into
the system. Continue to add refrigerant into the system until the specified
weight of R-12 has been added. Then, close the charging cylinder valve and
allow the system to pull any remaining refrigerant from the hose. When the
suction pressure drops to approximately 30 psi, close the gauge set center hose
valve.
- Operate the system until the pressures stabilize to verify normal operation
and system pressures.
- In high ambient temperatures, it may be necessary to operate a high volume
fan positioned to blow air through the condenser and radiator to aid in cooling
the engine and prevent excessive refrigerant system pressures.
- When charging is complete, close the valves at the ends of the low and high
hoses if not equipped with automatic closing valves. Then, disconnect the
manifold gauge set hoses from the vehicle and install the protective caps on
the service gauge port fittings.